INDUSTRIAL CONTROL PANELS
Active Harmonic Filter Panels
An active harmonic filter panel uses power electronics to inject a controlled compensating current into an electrical network. A shunt AHF is connected in parallel with the system and uses current measurement to address selected harmonic components within its compensation capability.
DriveTechno supports AHF panel and power quality enquiries across the UAE. Filter selection starts with measurements and a defined connection point. Send the network single-line diagram, harmonic report and major load details so the required current rating, CT arrangement and performance criteria can be reviewed before equipment is proposed.

Harmonic Mitigation

CT Measurement

Power Quality Analysis
Active Harmonic Filter Panel Solutions
An active harmonic filter panel uses power electronics to inject a controlled compensating current into an electrical network. A shunt AHF is connected in parallel with the system and uses current measurement to address selected harmonic components within its compensation capability.DriveTechno supports AHF panel and power quality enquiries across the UAE. Filter selection starts with measurements and a defined connection point. Send the network single-line diagram, harmonic report and major load details so the required current rating, CT arrangement and performance criteria can be reviewed before equipment is proposed.
Typical Applications

Facilities with significant nonlinear motor drive loads

Commercial and industrial distribution systems

Networks with documented harmonic performance requirements

Expansion or replacement of existing active filtering systems
Sizing an AHF from Compensation Current
An AHF is normally rated by compensating current rather than the total kW of the connected load. Required capacity depends on the harmonic spectrum, changing load conditions and any other compensation assigned to the filter. The network voltage, three-wire or four-wire arrangement and installation environment also determine the suitable equipment configuration.
⚙ Technical Selection Checklist
| Selection Item | Information to Confirm |
|---|---|
| Measurement boundary | Proposed connection point, monitoring point and loads to be compensated |
| Harmonic data | Current and voltage distortion, spectrum, load profile and measurement duration |
| Network data | Voltage, frequency, supply capacity, earthing and available fault level |
| Compensation duty | Harmonic current requirement and any specified reactive or imbalance function |
| Wiring topology | Three-wire or four-wire system and neutral harmonic requirement |
| CT arrangement | CT quantity, ratio, position, polarity and connection to the selected filter |
| Installation and acceptance | Cooling, enclosure, expansion, communication and agreed test conditions |
CT Position and Network Interaction
The filter needs to measure the intended current at the correct boundary. CT placement and polarity depend on the selected filter topology and manufacturer instructions. Multiple sources, capacitor banks, parallel filters and distributed loads can affect the design. Existing compensation equipment should therefore be shown on the single-line diagram. Current THD, often written THDi, and voltage THD, THDv, describe different measurements. Total demand distortion TDD uses a demand current reference. A report should identify the quantities, reference currents and measurement location so its results can be compared with the stated acceptance criterion.
Harmonic Limits and Performance Assessment
Specify where performance will be assessed and under which load and supply conditions. IEEE 519, where required by the project, assesses relevant distortion limits at the defined point of common coupling. Current THD and total demand distortion use different reference currents and should not be treated as the same measure. A universal distortion percentage cannot be guaranteed from a panel rating alone.
Additional Compensation and Limitations
Some AHF designs can also provide reactive current or load balancing, with those functions sharing available capacity as the equipment defines. Four-wire applications can need neutral harmonic compensation that a three-wire unit cannot provide. An AHF on the supply network serves a different purpose from a VFD output reactor, dV/dt filter or sine-wave filter between a drive and motor.
AHF Commissioning and Power Quality Records
Commissioning can verify CT association, compensation settings, available current and communication points. Before and after measurements should use comparable operating conditions and the agreed assessment boundary. The quotation should identify any baseline survey, installation, load testing and reporting responsibilities so the performance review is meaningful.
Frequently Asked Questions
Can an AHF be selected from the total VFD power?
Will an AHF always produce a fixed THD result?
Can the same panel correct power factor and harmonics?
Request an Active Harmonic Filter Quotation
Send the following information with your enquiry. Existing drawings, photographs and equipment data can help clarify any details that are not yet available.
Single-line diagram and proposed installation point · Power quality report with harmonic spectrum and load profile · Voltage, frequency, supply and fault level information · CT details and existing capacitor or filtering equipment · Required harmonic criteria, measurement boundary and extra functions · Panel environment, communications and survey or installation scope
Email your enquiry to info@DriveTechno.ae. We will review the application and prepare a quotation against the agreed technical requirements and scope.